HMIs have several optional plug-in module, multiple modules configurations are possible.
This FAQ explains which modules combinations can be used on HMI.
Note: Plug-in modules are not supported in eSMART, JSmart, Handheld series.
Slot numbering explanation
Images on the left show rear view of eTOP504, eTOP605, eX705, eXware703 HMI.
Images on the left show rear view of 7 inches HMI, this is also valid for all others HMI models.
Slot#2 and Slot#4 are available only if plug-in module has the "bus extension connector".
Each slot carries three communication channels:
Note: It is not possible to stack two modules that are using the same type of interface.
Table below shows relation between modules and max number of modules that can be used into HMIs, based on their Interface Type:
Module | Application | Max modules on Platforms | Interface type | Bus extension connector |
PLCM01 PLCM01-CDS |
CAN CAN+CODESYS V2 License |
1 for UN31 / UN70 2 for all others |
CAN | Yes |
PLCM01-NE PLCM01-NEC |
CAN CAN+CODESYS V2 License |
1 for UN31 / UN70 2 for all others |
CAN | No |
PLCM02 | KNX KNX+CODESYS V2 License |
1 | Serial | No |
PLCM03 | Serial RS-232 | 1 for UN31 / UN70 2 for all others |
Serial | Yes |
PLCM04 | Serial RS485/422 | 1 for UN31 / UN70 2 for all others |
Serial | Yes |
PLCM05 PLCM05-CDS |
Bus Extender CODESYS V2 License |
1 | None | Yes |
PLCM06 | Profibus DP | 1 | SPI | No |
PLCM07 | Network separator | 1 * | None | Yes |
PLCM09 | 3G module | 1 ** | Serial | Yes |
PLIO03 PLIO03-CDS |
Multifunction I/O I/O+CODESYS V2 License |
1 | SPI | No |
PLIO04 | Multifunction I/O | 1 | SPI | No |
PLIO06 PLIO06-CDS |
Compact I/O I/O+CODESYS V2 License |
1 for UN31 / UN70 2 for all others |
SPI | No |
PLIO07 | Compact I/O | 1 for UN31 / UN70 2 for all others |
SPI | No |
* = PLCM07 module is intended to be used only with Windows CE HMIs (UN30/UN31), to permit network separation.
** = PLCM09 module is only supported on Linux HMIs
If PLCM03 and PLCM04 (additional serial ports) are used, COM port numbering is as following:
Platforms legend:
HMI series | Platform |
eTOP500: eTOP504, eTOP506, eTOP507 eTOP500 Glass: eTOP507G eTOP600: eTOP605 |
UN31 (Windows CE) |
eTOP500: eTOP507M, eTOP510, eTOP512, eTOP513, eTOP515 eTOP500 Glass: eTOP507MG, eTOP507MFB, eTOP510G, eTOP515G eTOP600: eTOP607M eTOP610 |
UN30 (Windows CE) |
eX700: eX707, eX707G, eX707FB, eX710, eX710G, eX715, eX715FB eX721 eXware: eXware707, eXware707Q |
UN65 (Linux) |
eX700: eX705 eXware: eXware703 |
UN70 (Linux) |